The eI/O-150 provides 4 optically isolated inputs and 4 SPDT Form C relay outputs. Inputs can
range from 5-30VDC and provide 300V isolation to ground, while the high current Form C
relays switch up to 60VDC @ 5A or 250VAC @ 6A. Each Form C relay has a discrete common
and includes normally-open and normally-closed contact connections. Field wiring is simplified
via 3.5mm field removable terminal blocks.
Outputs
Type
4 SPDT Form C relays
Power
DC 240W / AC 1200 VA
Contact Voltage
60VDC / 250VAC max. (5VDC min.)
Contact Current (DC)
<30 VDC @ 5A max.
>30 VDC @ 700mA max. (100mA min.)
Contact Current (AC)
6A max.